E. INTERCHANGE CLASSIFICATIONS (CONT.)

3. SCHEDULING

        At a minimum, the following practices will be used for Interchange Energy Transactions to ensure reliable operations of the ERCOT Interconnected System:

            a. The delivering and receiving Control Areas will confirm all parameters of each transaction prior to its initiation, change, or termination. Parameters to be confirmed include at least the following:

        • Amount
        • Start Date and Time
        • Stop Date and Time
        • Ramp Rates
        • Energy Type

4. INADVERTENT ENERGY

G. APPLICATION OF ANCILLARY SERVICES (CONT.)

e. Buyer and Seller Obligations

    1. At no time shall the rate of change of load scanned at the slower scan rate cause the ACE of the interconnected Control Areas to change more than either can recover in 15 seconds. This slower scan rate is intended only for unidirectional ties that serve loads that have a slow rate of change such as residential loads. Non-conforming loads such as arc furnaces and other fast changing industrial loads do not qualify for the slower scan rate. Generators or interruptible loads will not qualify for the slower scan rate.
    2. The total peak value of all unidirectional interconnects scanned at a rate slower than 4 seconds shall not exceed 5% of the yearly peak load of the Control Area.
    3. If an interconnection is scanned at a rate less frequently than once every 4 seconds, both Control Areas must agree.

3. Digital Telemetry

a. Definition

b. Defined Equipment

c. Equipment Standards

d. Dual or Multiple Porting

e. Accuracy

4. Analog Telemetry

a. Definition

Control Area: ________________ Generation Entity: _________________ Unit Name:__________________

Date: Start Time of Reactive Test:

Unit Net Load at Time of Test: MW Temperature at Plant (° F):

Gross Generation MW Auxiliary Load MW

Maximum Reactive Operating Limit Observed for:

Lagging Power Factor: Max. Reactive Capability

Leading Power Factor: Max. Reactive Capability

Operating Hydrogen Pressure during the Test: LB.

VAR Reading Location: Transmission Bus Voltage at the Time of the Test: kV

(Generator output terminal preferred) (Identify if maximum or minimum operating limit)

Generator Terminal Voltage kV

Abnormal Conditions at Time of Test:

Factors that Limited Reactive Capability During Test:

Gen. Ent. Rep.:_______________ Control Area Rep.:_________________ ISO Rep.:

B. TRANSMISSION SECURITY CRITERIA

a. Uncontrolled breakup of the transmission system,

d. Customer outages, except for high set interruptible and radially served loads.

Level