- Home
- Market Rules
- Issues
NPRR1052
Summary
Title | Load Zone Pricing for Settlement Only Storage Prior to NPRR995 Implementation |
---|---|
Next Group | |
Next Step | |
Status | Approved on 02/09/2021 |
Effective Dates |
02/11/2022
|
Action
Date | Gov Body | Action Taken | Next Steps |
---|---|---|---|
02/09/2021 | BOARD | Approved | |
01/27/2021 | TAC | Recommended for Approval | Board for consideration |
12/10/2020 | PRS | Recommended for Approval | TAC for consideration |
11/11/2020 | PRS | Recommended for Approval | PRS for Impact Analysis consideration |
Voting Record
Date | Gov Body | Motion | Result |
---|---|---|---|
02/09/2021 | BOARD | To approve NPRR1052 as recommended by TAC in the 1/27/21 TAC Report | Passed |
01/27/2021 | TAC | To recommend approval of NPRR1052 as recommended by PRS in the 12/10/20 PRS Report | Passed |
12/10/2020 | PRS | To endorse and forward to TAC the 11/11/20 PRS Report and Impact Analysis for NPRR1052 | Passed |
11/11/2020 | PRS | To recommend approval of NPRR1052 as submitted | Passed |
Background
Status: | Approved |
---|---|
Date Posted: | Oct 27, 2020 |
Sponsor: | ERCOT |
Urgent: | No |
Sections: | 6.6.3.2, 6.6.3.9, 9.19.1, and 16.5 |
Description: | This NPRR establishes the following Settlement and metering provisions for Energy Storage Systems (ESSs) that are registered as Settlement Only Generators (SOGs) pending the approval and implementation of NPRR995, RTF-6 Create Definition and Terms for Settlement Only Energy Storage: (1) For any site with one or more ESS SOGs where the ESSs’ rated capacity constitutes more than 50% of the site’s overall nameplate capacity, energy injections and withdrawals will be settled at the Load Zone price; and (2) For any site with one or more ESS SOGs where the ESSs’ rated capacity constitutes 50% or less of the site’s overall nameplate capacity, energy injections will be settled at the applicable nodal price and withdrawals will be settled at the Load Zone price. This is the only scenario in which zonal/nodal arbitrage is possible. ERCOT expects that such configurations will be minimal, and emphasizes that this arbitrage possibility will expire upon implementation of NPRR995. |
Reason: | Market efficiencies or enhancements |
Key Documents
Oct 27, 2020 - docx - 76.1 KB
Oct 27, 2020 - docx - 28.6 KB
Nov 16, 2020 - xls - 129.5 KB
Nov 16, 2020 - docx - 76.1 KB
Dec 15, 2020 - xls - 129.5 KB
Dec 15, 2020 - docx - 76.2 KB
Jan 29, 2021 - xls - 101 KB
Jan 29, 2021 - docx - 78.2 KB
Feb 10, 2021 - docx - 78.6 KB