NPRR892
Summary
Title
Non-Spin Reserve Energy Floor Clarification
Next Group
Next Step
Status
Approved on 12/11/2018
Effective Dates
Voting Record
Date
Gov Body
Motion
Result
12/11/2018
BOARD
approved NPRR892 as recommended by TAC in the 11/29/18 TAC Report
Passed
11/29/2018
TAC
to recommend approval of NPRR892 as recommended by PRS in the 11/15/18 PRS Report
Passed
11/15/2018
PRS
to endorse and forward to TAC the 10/18/18 PRS Report and Impact Analysis for NPRR892
Passed
10/18/2018
PRS
to recommend approval of NPRR892 as amended by the 10/5/18 ERCOT comments
Passed
09/13/2018
PRS
to table NPRR892 for one month
Passed
Background
Status:
Approved
Date Posted:
Aug 22, 2018
Sponsor:
Morgan Stanley
Urgent:
No
Sections:
6.4.4.1
Description:
This Nodal Protocol Revision Request (NPRR) places a floor on energy on units carrying Non-Spinning Reserves (Non-Spin) and Responsive Reserves (RRS) and/or Regulation Up Service (Reg-Up) concurrently to ensure the Non-Spin capacity is priced above the $75/MWh floor.
Reason:
Addresses current operational issues