PGRR046
Summary
| Title | Addition of Geomagnetically Induced Current (GIC) Model Building Requirements |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 10/11/2016 |
| Effective Dates |
09/01/2016
Section 2.2 05/08/2017
Section 6.11 |
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 10/11/2016 | BOARD | Approved | |
| 07/28/2016 | TAC | Recommended for Approval | Revision Request Consideration |
| 07/07/2016 | ROS | Recommended for Approval | Revision Request Consideration |
| 06/29/2016 | PLWG | Recommended for Approval | Revision Request Consideration |
| 05/18/2016 | PLWG | Recommended for Approval | Impact Analysis Consideration |
| 04/20/2016 | PLWG | Deferred/Tabled | Language Consideration |
| 03/23/2016 | PLWG | Deferred/Tabled | Language Consideration |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 10/11/2016 | BOARD | To approve PGRR046 as recommended by TAC in the 7/28/16 TAC Report with an ERCOT Board action effective date of 8/9/16. | Passed |
| 07/28/2016 | TAC | To recommend approval of PGRR046 as recommended by ROS in the 7/7/16 ROS Report. | Passed |
| 07/07/2016 | ROS | To recommend approval of PGRR046 as recommended by PLWG in the 6/29/16 PLWG Report. | Passed |
| 06/29/2016 | PLWG | To endorse and forward to ROS the 5/18/16 PLWG Report as revised by PLWG and the Revised Impact Analysis for PGRR046. | Passed |
| 05/18/2016 | PLWG | To recommend approval of PGRR046 as amended by the 4/19/16 Wind Coalition comments as revised by PLWG. | Passed |
| 04/20/2016 | PLWG | To table PGRR046 for one month. | Passed |
| 03/23/2016 | PLWG | To table PGRR046 for one month. | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Feb 26, 2016 |
| Sponsor: | ERCOT |
| Urgent: | No |
| Sections: | 2.2, 6.11(new) |
| Description: | This Planning Guide Revision Request (PGRR) aligns the Planning Guides with North American Electric Reliability Corporation (NERC) Reliability Standard TPL-007-1, Transmission System Planned Performance for Geomagnetic Disturbance Events, by specifying a process for developing geomagnetically-induced current system models. |
| Reason: | Regulatory requirements |
Key Documents
Feb 26, 2016 - doc - 85.5 KB
Feb 26, 2016 - doc - 56.5 KB
Mar 24, 2016 - doc - 82 KB
Apr 14, 2016 - doc - 42.5 KB
Apr 19, 2016 - doc - 44 KB
Apr 19, 2016 - doc - 45 KB
Apr 22, 2016 - doc - 84 KB
May 20, 2016 - doc - 88 KB
Jun 22, 2016 - doc - 56.5 KB
Jun 29, 2016 - doc - 90 KB
Jul 8, 2016 - doc - 91 KB
Jul 29, 2016 - doc - 94 KB
Oct 13, 2016 - doc - 95.5 KB