PGRR075
Summary
| Title | Dynamic Model Quality Requirement |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 04/14/2020 |
| Effective Dates |
05/01/2020
|
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 04/14/2020 | BOARD | Approved | |
| 04/03/2020 | TAC | Recommended for Approval | Revision Request Consideration |
| 02/06/2020 | ROS | Recommended for Approval | Revision Request Consideration |
| 01/09/2020 | ROS | Recommended for Approval | Impact Analysis Consideration |
| 11/07/2019 | ROS | Deferred/Tabled | Language Consideration |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 04/14/2020 | BOARD | to approve PGRR075 as recommended by TAC in the 4/3/20 TAC Report | Passed |
| 04/03/2020 | TAC | to recommend approval of PGRR075 as recommended by ROS in the 2/6/20 ROS Report | Passed |
| 02/06/2020 | ROS | to endorse and forward to TAC the 1/9/20 ROS Report and the Impact Analysis for PGRR075 | Passed |
| 01/09/2020 | ROS | to recommend approval of PGRR075 as amended by the 11/22/19 ERCOT comments | Passed |
| 11/07/2019 | ROS | to table PGRR075 and refer the issue to the Dynamics Working Group (DWG) and Planning Working Group (PLWG) | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Oct 22, 2019 |
| Sponsor: | ERCOT |
| Urgent: | No |
| Sections: | 5.7.1, 6.2, 6.2.2, 6.2.4, 6.2.5 (delete) |
| Description: | This Planning Guide Revision Request (PGRR) adds a requirement for Resource Entities and Interconnecting Entities (IEs) to provide model quality test results that demonstrate appropriate performance for submitted dynamic models. Additional revisions are proposed to: Clarify that dynamic model data shall be provided using the appropriate dynamic model template; Raise awareness of requirements associated with user written dynamic models (move from Dynamics Working Group Procedure Manual to Planning Guide); Make various miscellaneous language updates and corrections, including the elimination of Section 6.2.5, which has been superseded by North American Electric Reliability Corporation (NERC) Reliability Standard PRC-002-2, Disturbance Monitoring and Reporting Requirements, and Nodal Operating Guide Section 6.1.3, Phasor Measurement Recording Equipment Including Dynamic Disturbance Recording Equipment. |
| Reason: | Other: Improve dynamic model quality in alignment with 2019 Reliability and Operations Subcommittee (ROS) goals |
Key Documents
Oct 22, 2019 - docx - 56.3 KB
Oct 22, 2019 - doc - 54 KB
Nov 11, 2019 - docx - 53.5 KB
Nov 11, 2019 - doc - 70.5 KB
Nov 22, 2019 - doc - 71 KB
Dec 13, 2019 - doc - 40.5 KB
Dec 16, 2019 - doc - 39 KB
Jan 13, 2020 - doc - 118 KB
Feb 7, 2020 - doc - 119 KB
Apr 6, 2020 - xls - 128.5 KB
Apr 6, 2020 - doc - 122.5 KB
Apr 16, 2020 - doc - 123 KB