NPRR1029
Summary
Title | BESTF-6 DC-Coupled Resources |
---|---|
Next Group | |
Next Step | |
Status | Approved on 12/08/2020 |
Action
Date | Gov Body | Action Taken | Next Steps |
---|---|---|---|
12/08/2020 | BOARD | Approved | |
11/18/2020 | TAC | Recommended for Approval | Board for consideration |
11/11/2020 | PRS | Recommended for Approval | TAC for consideration |
07/16/2020 | PRS | Deferred/Tabled | PRS for consideration |
Voting Record
Date | Gov Body | Motion | Result |
---|---|---|---|
12/08/2020 | BOARD | To approve NPRR1029 as recommended by TAC in the 11/18/20 TAC Report | Passed |
11/18/2020 | TAC | To recommend approval of NPRR1029 as recommended by PRS in the 11/11/20 PRS Report | Passed |
11/11/2020 | PRS | To grant NPRR1029 Urgent status; to recommend approval of NPRR1029 as amended by the 10/30/20 ERCOT comments; and forward to TAC NPRR1029 and the Impact Analysis with a recommended priority of 2020 and rank of 3015 | Passed |
07/16/2020 | PRS | To table NPRR1029 | Passed |
Background
Status: | Approved |
---|---|
Date Posted: | Jun 26, 2020 |
Sponsor: | ERCOT |
Urgent: | Yes |
Sections: | 2.1, 3.2.1, 3.2.3, 3.8.7 (new), 3.9.1, 3.13, 3.15, 4.2.2, 4.2.3, 5.7.4.1.1, 6.5.5.2, 6.5.7.5, 6.5.7.11 (new), 6.6.5, 6.6.5.5, 6.6.5.5.1, 8.1.1.4.1, 25.5.2, 25.5.5, and 25.5.6 |
Description: | This Nodal Protocol Revision Request (NPRR) enables the integration of DC-Coupled Resources into ERCOT’s core systems. DC-Coupled Resources are defined as a type of Energy Storage Resource (ESR) and will be required to follow all rules associated with ESRs in addition to meeting the additional requirements in this NPRR. The language in this NPRR applies to both the current combo model era, in which ESRs are treated in ERCOT systems as two Resources—a Generation Resource and a Controllable Load Resource—as well as the future single model era described in NPRR1014, BESTF-4 Energy Storage Resource Single Model. |
Reason: | Addresses current operational issues / Market efficiencies or enhancements |
Key Documents
Jun 26, 2020 - docx - 190.1 KB
Jun 26, 2020 - docx - 28.8 KB
Jul 21, 2020 - xls - 130 KB
Jul 23, 2020 - docx - 200.8 KB
Sep 24, 2020 - docx - 216.6 KB
Oct 30, 2020 - docx - 269.3 KB
Nov 13, 2020 - xls - 130 KB
Nov 13, 2020 - docx - 280.1 KB
Nov 24, 2020 - xls - 130 KB
Nov 24, 2020 - docx - 281.2 KB
Dec 10, 2020 - docx - 279.3 KB