- Home
- Market Rules
- Issues
NPRR1098
Summary
Title | Direct Current Tie (DC Tie) Reactive Power Capability Requirements |
---|---|
Next Group | |
Next Step | |
Status | Approved on 03/31/2022 |
Action
Date | Gov Body | Action Taken | Next Steps |
---|---|---|---|
03/31/2022 | PUCT | Approved | |
03/07/2022 | BOARD | Recommended for Approval | Revision Request Consideration |
01/31/2022 | TAC | Recommended for Approval | Revision Request Consideration |
12/14/2021 | PRS | Recommended for Approval | Revision Request Consideration |
11/10/2021 | PRS | Deferred/Tabled | Impact Analysis Consideration |
10/14/2021 | PRS | Recommended for Approval | Impact Analysis Consideration |
Voting Record
Date | Gov Body | Motion | Result |
---|---|---|---|
03/31/2022 | PUCT | to approve NPRR1098 and accompanying ERCOT Market Impact Statement as presented in Project No. 52934, Review of Rules Adopted by the Independent Organization | Passed |
03/07/2022 | BOARD | to recommend approval of NPRR1098 as recommended by TAC in the 1/31/22 TAC Report | Passed |
01/31/2022 | TAC | to recommend approval of NPRR1098 as recommended by PRS in the 12/14/21 PRS Report | Passed |
12/14/2021 | PRS | to endorse and forward to TAC the 11/10/21 PRS Report as amended by the 11/29/21 ERCOT comments and the Impact Analysis for NPRR1098 with a recommended priority of 2022 and rank of 2530 | Passed |
11/10/2021 | PRS | To table NPRR1098 | Passed |
10/14/2021 | PRS | to recommend approval of NPRR1098 as submitted | Passed |
Background
Status: | Approved |
---|---|
Date Posted: | Sep 29, 2021 |
Sponsor: | ERCOT |
Urgent: | No |
Sections: | 2.1, 3.15.1, 3.15.4 (new), and 6.5.6 |
Description: | This Nodal Protocol Revision Request (NPRR) establishes Reactive Power capability requirements for new Direct Current Ties (DC Ties) interconnecting to the ERCOT System and existing DC Ties replaced after January 1, 2021. |
Reason: | Regulatory Requirements |
Key Documents
Sep 29, 2021 - doc - 97.5 KB
Sep 29, 2021 - docx - 30.8 KB
Oct 19, 2021 - xls - 114.5 KB
Oct 19, 2021 - doc - 106 KB
Nov 1, 2021 - doc - 83.5 KB
Nov 15, 2021 - xls - 143.5 KB
Nov 15, 2021 - doc - 108 KB
Nov 29, 2021 - doc - 103 KB
Dec 15, 2021 - xls - 143.5 KB
Dec 15, 2021 - doc - 132.5 KB
Feb 3, 2022 - xls - 141.5 KB
Feb 3, 2022 - doc - 133 KB
Mar 10, 2022 - doc - 166 KB
Apr 1, 2022 - doc - 137 KB