- Home
- Market Rules
- Issues
NPRR1101
Summary
Title | Create Non-Spin Deployment Groups made up of Generation Resources Providing Off-Line Non-Spinning Reserve and Load Resources that are Not Controllable Load Resources Providing Non-Spinning Reserve |
---|---|
Next Group | |
Next Step | |
Status | Approved on 12/16/2021 |
Effective Dates |
05/27/2022
|
Action
Date | Gov Body | Action Taken | Next Steps |
---|---|---|---|
12/16/2021 | PUCT | Approved | |
12/10/2021 | BOARD | Recommended for Approval | PUCT for Consideration |
11/29/2021 | TAC | Recommended for Approval | Board for consideration |
11/10/2021 | PRS | Recommended for Approval | TAC for consideration |
Voting Record
Date | Gov Body | Motion | Result |
---|---|---|---|
12/16/2021 | PUCT | To approve NPRR1101 and accompanying ERCOT Market Impact Statement as presented in Project No. 52307, Review of Rules Adopted by the Independent Organization in Calendar Year 2021 | Passed |
12/10/2021 | BOARD | To recommended approval of NPRR1101 as recommended by TAC in the 11/29/21 TAC Report. | Passed |
11/29/2021 | TAC | To recommend approval of NPRR1101 as recommended by PRS in the 11/10/21 PRS Report as amended by the 11/19/21 ERCOT comment. | Passed |
11/10/2021 | PRS | To grant NPRR1101 Urgent status; to recommend approval of NPRR1101 as submitted; and to forward to TAC NPRR1101 and the Impact Analysis with a recommended priority of 2022 and rank of 3195 | Passed |
Background
Status: | Approved |
---|---|
Date Posted: | Oct 20, 2021 |
Sponsor: | ERCOT |
Urgent: | Yes |
Sections: | 6.5.7.6.2.3 |
Description: | This NPRR modifies the deployment grouping requirements for Load Resources that are not Controllable Load Resources (“NCLRs”) providing Non-Spinning Reserve (Non-Spin) to include Generation Resources providing Off-Line Non-Spin. This deployment grouping process only addresses NCLR and Off-Line Generation Resources. Other Resources providing Non-Spin are not addressed in the proposed revisions. |
Reason: | Addresses current operational issues. Market efficiencies or enhancements |
Key Documents
Oct 20, 2021 - docx - 30.6 KB
Nov 8, 2021 - docx - 30.5 KB
Nov 12, 2021 - xls - 101 KB
Nov 12, 2021 - xls - 111.5 KB
Nov 12, 2021 - docx - 50.1 KB
Nov 19, 2021 - docx - 32.1 KB
Nov 30, 2021 - xls - 102 KB
Nov 30, 2021 - docx - 51.7 KB
Dec 10, 2021 - docx - 51.8 KB
Dec 20, 2021 - docx - 52.4 KB