- Home
- Market Rules
- Issues
NPRR166
Summary
Title | Timing for Required Black Start Unit Load Carrying Test |
---|---|
Next Group | |
Next Step | |
Status | Approved on 05/20/2009 |
Effective Dates |
12/01/2010
or per the Nodal Protocol Transition Plan http://www.ercot.com/mktrules/protocols (06/01/09 Nodal Protocols Library) |
Action
Date | Gov Body | Action Taken | Next Steps |
---|---|---|---|
04/23/2009 | PRS | Recommended for Approval | TAC Consideration |
03/19/2009 | PRS | Recommended for Approval | PRS Impact Analysis Review |
05/07/2009 | TAC | Recommended for Approval | ERCOT Board consideration |
05/20/2009 | BOARD | Approved | |
12/18/2008 | PRS | Referred | PRS Consideration |
Voting Record
Date | Gov Body | Motion | Result |
---|---|---|---|
04/23/2009 | PRS | To endorse and forward the PRS Recommendation Report and Impact Analysis for NPRR166 to TAC | Passed |
03/19/2009 | PRS | To recommend approval of NPRR166 as submitted | Passed |
05/07/2009 | TAC | to recommend approval of NPRR166 as recommended by PRS | Passed |
05/20/2009 | BOARD | To approve NPRR166 as recommended by TAC. | Passed |
12/18/2008 | PRS | To refer NPRR166 to TPTF for review. | Passed |
Background
Status: | Approved |
---|---|
Date Posted: | Nov 20, 2008 |
Sponsor: | ERCOT |
Urgent: | No |
Sections: | 8.1.1.2.1.5 |
Description: | This Nodal Protocol Revision Request (NPRR) synchronizes the Nodal Protocols with changes being proposed to the zonal Protocols through Protocol Revision Request (PRR) 785. This NPRR changes the required Black Start Unit Load Carrying Test from once every six years to once every five years. |
Reason: | North American Electric Reliability Corporation (NERC) requires Black Start Unit Testing at a minimum of every five years. This change reduces ambiguity and risk of a NERC compliance violation. |
Key Documents
Nov 20, 2008 - doc - 93.5 KB
Nov 20, 2008 - doc - 48 KB
Dec 3, 2008 - doc - 39.5 KB
Dec 19, 2008 - doc - 92.5 KB
Feb 24, 2009 - doc - 67 KB
Mar 20, 2009 - doc - 86.5 KB
Apr 17, 2009 - doc - 139.5 KB
Apr 21, 2009 - doc - 45.5 KB
Apr 27, 2009 - doc - 88 KB
May 8, 2009 - doc - 89 KB
May 22, 2009 - doc - 91 KB