NPRR999
Summary
| Title | DC Tie Ramp Limitations |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 10/13/2020 |
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 10/13/2020 | BOARD | Approved | |
| 09/23/2020 | TAC | Recommended for Approval | Revision Request Consideration |
| 09/10/2020 | PRS | Recommended for Approval | Revision Request Consideration |
| 08/13/2020 | PRS | Deferred/Tabled | Impact Analysis Consideration |
| 07/16/2020 | PRS | Recommended for Approval | Impact Analysis Consideration |
| 06/11/2020 | PRS | Deferred/Tabled | Language Consideration |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 10/13/2020 | BOARD | to approve NPRR999 as recommended by TAC in the 9/23/20 TAC Report | Passed |
| 09/23/2020 | TAC | to recommend approval of NPRR999 as recommended by PRS in the 9/10/20 PRS Report | Passed |
| 09/10/2020 | PRS | to endorse and forward to TAC the 8/13/20 PRS Report and Revised Impact Analysis for NPRR999 | Passed |
| 08/13/2020 | PRS | to table NPRR999 | Passed |
| 07/16/2020 | PRS | to recommend approval of NPRR999 as amended by the 7/2/20 ERCOT comments | Passed |
| 06/11/2020 | PRS | to table NPRR999 | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Feb 20, 2020 |
| Sponsor: | ERCOT |
| Urgent: | No |
| Sections: | 4.4.4 and 4.4.4.3 (new) |
| Description: | This Nodal Protocol Revision Request (NPRR) revises Protocol Section 4.4.4 and creates new Protocol Section 4.4.4.3 to clarify that, in those cases where ERCOT determines that system conditions show insufficient ramp capability to meet the sum of all Direct Current Ties’ (DC Ties’) scheduled ramp, ERCOT may either (1) curtail DC Tie schedules or (2) require DC Tie Operators to resubmit e-Tags with an adjusted ramp duration. This NPRR is proposed in accordance with the May 23, 2017, order of the Public Utility Commission of Texas (PUCT) in Project No. 46304, Oversight Proceeding Regarding ERCOT Matters Arising Out of PUC Docket No. 45624 Relating to DC Tie Project Proposed by Southern Cross Transmission, LLC, which requires ERCOT to address a number of issues as a condition for the energization of the DC Tie project proposed by Southern Cross Transmission LLC (“Southern Cross”). Relevant here, Directive 3 in the order requires ERCOT to “determine what ramp rate restrictions, if any, will be necessary to accommodate the interconnection of the Southern Cross DC Tie.” |
| Reason: | Regulatory requirements |
Key Documents
Feb 20, 2020 - doc - 89.5 KB
Feb 20, 2020 - docx - 29 KB
Jun 16, 2020 - xls - 110.5 KB
Jun 16, 2020 - doc - 97.5 KB
Jul 2, 2020 - doc - 82 KB
Jul 21, 2020 - xls - 130 KB
Jul 21, 2020 - doc - 97 KB
Aug 18, 2020 - xls - 100.5 KB
Aug 18, 2020 - doc - 98.5 KB
Aug 28, 2020 - docx - 29.6 KB
Sep 15, 2020 - xls - 129.5 KB
Sep 15, 2020 - doc - 101.5 KB
Sep 28, 2020 - xls - 130 KB
Sep 28, 2020 - doc - 104 KB
Oct 16, 2020 - doc - 104.5 KB