PRR788
Summary
| Title | Ramp Rate Limits for Existing WGRs | 
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 01/20/2009 | 
| Effective Dates | 
                   02/01/2009 
                   | 
            
Action
| Date | Gov Body | Action Taken | Next Steps | 
|---|---|---|---|
| 01/20/2009 | BOARD | Approved | |
| 01/08/2009 | TAC | Recommended for Approval | ERCOT Board consideration of PRR788 | 
| 12/18/2008 | PRS | Recommended for Approval | TAC consideration of PRR788 | 
Voting Record
| Date | Gov Body | Motion | Result | 
|---|---|---|---|
| 01/20/2009 | BOARD | To approve PRR788 as recommended by TAC. | Passed | 
| 01/08/2009 | TAC | To recommend approval of PRR788 as recommended by PRS. | Passed | 
| 12/18/2008 | PRS | To recommend approval of PRR788 as amended by Luminant comments and as revised by PRS. | Passed | 
Background
| Status: | Approved | 
|---|---|
| Date Posted: | Dec 9, 2008 | 
| Sponsor: | FPLEnergy | 
| Urgent: | Yes | 
| Sections: | 6.5.13 | 
| Description: | This PRR proposes a requirement that certain existing WGRs limit the unit ramp rate to ten percent (10%) per minute of their nameplate capacity ratings as registered with ERCOT. | 
| Reason: | This PRR is a follow-up to PRR771, which required ramp rate limitations for WGRs with signed Interconnection Agreements on or after Jan. 1, 2009. This PRR addresses units with signed Interconnection Agreements prior to Jan. 1, 2009. | 
Key Documents
                Dec 9, 2008 - doc - 95.5 KB
            
        
                Dec 11, 2008 - xls - 21.5 KB
            
        
                Dec 15, 2008 - doc - 50.5 KB
            
        
                Dec 19, 2008 - doc - 97 KB
            
        
                Dec 30, 2008 - doc - 44.5 KB
            
        
                Jan 8, 2009 - doc - 100.5 KB
            
        
                Jan 21, 2009 - doc - 100 KB