SMOGRR025
Summary
Title | Modifications to Line Loss Compensation Requirement for EPS Metering |
---|---|
Next Group | |
Next Step | |
Status | Approved on 05/12/2022 |
Effective Dates |
06/01/2022
|
Action
Date | Gov Body | Action Taken | Next Steps |
---|---|---|---|
05/12/2022 | PUCT | Approved | |
04/28/2022 | BOARD | Recommended for Approval | Revision Request Consideration |
04/13/2022 | TAC | Recommended for Approval | Revision Request Consideration |
04/06/2022 | WMS | Recommended for Approval | Revision Request Consideration |
03/02/2022 | WMS | Recommended for Approval | Impact Analysis Consideration |
Voting Record
Date | Gov Body | Motion | Result |
---|---|---|---|
05/12/2022 | PUCT | to approve SMOGRR025 and accompanying ERCOT Market Impact Statement as presented in Project No. 52934, Review of Rules Adopted by the Independent Organization | Passed |
04/28/2022 | BOARD | to recommend approval of SMOGRR025 as recommended by TAC in the 4/13/22 TAC Report | Passed |
04/13/2022 | TAC | to recommend approval of SMOGRR025 as recommended by WMS in the 4/6/22 WMS Report | Passed |
04/06/2022 | WMS | to endorse and forward to TAC the 3/2/22 WMS Report and Impact Analysis for SMOGRR025 | Passed |
03/02/2022 | WMS | to recommend approval of SMOGRR025 as submitted | Passed |
Background
Status: | Approved |
---|---|
Date Posted: | Jan 21, 2022 |
Sponsor: | ERCOT |
Urgent: | No |
Sections: | 8.4 |
Description: | This Settlement Metering Operating Guide Revision Request (SMOGRR) allows for losses in short runs of connecting lines to be disregarded in instances where the ERCOT-Polled Settlement (EPS) Meter is not physically placed at the Point of Interconnection (POI). This SMOGRR requires calculation to verify that the watts copper losses are below 0.001%. |
Reason: | Addresses current operational issues; Market efficiencies or enhancements |
Key Documents
Jan 21, 2022 - doc - 74.5 KB
Jan 21, 2022 - doc - 55 KB
Mar 7, 2022 - xls - 143 KB
Mar 7, 2022 - doc - 110 KB
Apr 8, 2022 - xls - 142 KB
Apr 8, 2022 - doc - 81.5 KB
Apr 18, 2022 - xls - 140 KB
Apr 18, 2022 - doc - 85.5 KB
May 2, 2022 - doc - 87 KB
May 17, 2022 - doc - 88.5 KB