Final Winterization Report: Texas Grid Ready for Winter Weather Operations
AUSTIN, TX, Jan. 18, 2022 – The Electric Reliability Council of Texas (ERCOT) today filed its final winter weatherization readiness report of the season with the Public Utility Commission of Texas. The report shows 321 out of 324 electric generation units and transmission facilities fully passed inspection for new winterization regulations from the Commission.
“The Texas electric grid is more prepared for winter operations than ever before,” said Interim ERCOT CEO Brad Jones.
ERCOT conducted onsite inspections at 302 electric generation units during December, representing 85 percent of the megawatt hours lost during Winter Storm Uri due to outages and 22 transmission station facilities. Three resources have been identified for further review but remain operational. They represent approximately 0.4 percent of the total ERCOT generation fleet.
“We are confident these 321 inspected facilities either meet or go beyond the new requirements from the Commission and we will continue to work with the other 3 facilities to ensure they correct remaining deficiencies,” said Woody Rickerson, ERCOT Vice President of System Planning and Weatherization. “Our teams spent thousands of hours preparing for and conducting these 324 on-site inspections to ensure the electric grid is prepared for winter.”
Results as of January 17, 2022: 324 ERCOT On-Site Inspections
at 302 Generation Facilities and 22 Transmission Facilities
Generation Units, all deficiencies cleared |
Generation Units with remaining deficiencies |
Transmission Facilities, all deficiencies cleared |
Transmission Facilities with remaining deficiencies |
299 |
3 |
22 |
0 |
The Commission will determine any potential enforcement actions resulting from the inspections. Last year, the Texas Legislature increased the maximum penalties for violating weatherization rules to $1,000,000 per day per violation.
- end -
ERCOT Communications